Kyn61-40.5 switchgear

Kyn61-40.5 switchgear

KYN61-40.5 removable AC metal-clad switchgear applies to 40.5kV, 3 phase, AC and 50/60Hz electrical power network for receiving and distributing power energy and also for control, monitor and protection. It is applicable in general power system.

Structure Description:
 
Switchgear according G83906 and IEC298 standards and design,And can be removed from the cabinet as a whole unit (trolley )components .
Cabinet structure are made of aluminum deposited zine plate or galvanized sheet assembled with both connection ,separate circuit breaker switchgear roon ,bus room ,cable room and instrument room,All metal components are grounded ,each compartment of the main circuit .system have separate pressure release channel in the cable compartment can be set 10*60mm ground bus .

Main characteristics:

1.The use of assembled cabinet structure ,circuit breaker handcart floorstanding structure ,
Samall size:
2.Optional: The company vacuum breaker VW1-40.5,xiamen huadian vacumm breaker VEP-40.5 ,similar circuit breaker are interchangeable .
3.Equipped with special transport vehicles can lift ,transport vehicles amd cabinet accurate positioning ,locking and reliable 
4.The main switch ,handcart ,door interlock switch between mandatory mechanical locking methods are used to meet the ‘Five Anti’ interlock function .
5.all operation can be carried out at the door closed state ,to protect the safety of the operator .
6.Cable ample room space ,can be connected to multiple cables ,and overhead outlet .
7.Shell protection grade IP3X,handcart room door open between the various compartments protection class IP2X.
8.The material can be galvanized sheet can be deposited alumimum zinc plate production .

Main Electric Parameters
 
No. Items Unit  Parameters
1  Rated voltage KV 40.5
2  Rated frequency Hz 50
3   The main busbar rated current A 1250,1600,1200
4   Branch busbar rated current A 630/1250/ 1600
5        Rated insulation level    Power frequency withstand voltage in 1min  (Effective value) Phase-phase,
Phase-ground
KV 95
         
 Primary isolation fracture
KV 115
 Lightning Impulse Withstand Voltage
(peak value)
Phase-phase,
Phase-ground
KV 185
        
 Primary isolation fracture
KV 215
   Power frequency withstand voltage of auxiliary control circuit   V 2000
6       Rated short circuit breaking current KA 25/31.5
7  Rated short circuit closing current (peak value) KA 63/80
8   Rated short-time withstand current (4S) KA 25/31.5
9    Rated peak withstand current KA 63/80
10  Rated voltage of auxiliary control circuit V  -110,-220,~220
11   Protection grade   Enclosure IP4X, IP2X When the door of the circuit breaker opens
12  Outline size (width * depth * height) mm 1400(1200)*2800(2600)*2600(*includes an internal digital SF6 handcart scheme)
13   weight kg ~2300